New Arrivals Just Dropped – Explore the Latest in Tech, Home, and More!

Deep Sea  |  SKU: B07SJ5SXGN

DSE6020 MKII Original Deep Sea Generator Controller Module

Precio normal $1,347.75 USD
Los gastos de envío se calcularán al momento de pagar.

  • 30-Day Easy Returns
  • Tracked Shipping on Every Order
  • Secure & Encrypted Checkout
Apple Pay Diners ClubGoogle Pay Mastercard Shop Pay Visa

Questions? We reply fast: support@underyours.com

Returns

Request a return within 30 days of delivery on eligible items. Items must be unused and in original packaging; some items (like undergarments) aren't returnable for hygiene reasons. Full return policy

Descripción

Brand: Deep Sea

Color: Gray

Features:

  • DSE6020 AMF module,The control system is an integral part of the unit and also the heart of the unit. The application of the intelligent control system in the unit is helpful to improving the quality of the electric energy and the automation level of the diesel unit.
  • Three-remote” communication fully automatic control screen: On the basis of the “self-start control screen” function, it also has the communication mode.
  • Self-start control screen: The unit can realize both local manual control and remote control (by the external signal line). You need to connect the signal control line to this screen correctly.
  • Electronics Generator Controller DSE6020 MKII is used in the automation and monitoring system of single unit. It has many functions like automatic startup/shutdown, data measurement, alarm protection and “three-remote". The controller has large LCD display and Chinese/English interface, realizing simple operation and reliable running.
  • Standard screen: Namely manual control screen. You only need to connect the start battery to control the unit locally.

SPECIFICATION DC SUPPLY CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking. MAXIMUM OPERATING CURRENT 100 mA at 12 V, 105 mA at 24 V MAXIMUM STANDBY CURRENT 60 mA at 12 V, 55 mA at 24 V MAXIMUM SLEEP CURRENT 40 mA at 12 V, 35 mA at 24 V GENERATOR & MAINS (UTILITY) VOLTAGE RANGE 15 V to 415 V AC (Ph to N) 26 V to 719 V AC (Ph to Ph) FREQUENCY RANGE 3.5 Hz to 75 Hz INPUTS

DIGITAL INPUTS A to F Negative switching ANALOGUE INPUTS A to C Configurable as: Negative switching digital input 0 Ω to 480 Ω ANALOGUE INPUT D Configurable as: Negative switching digital input 0 V to 10 V 4 mA to 20 mA 0 Ω to 480 Ω OUTPUTS

OUTPUT A (FUEL) 10 A short term, 5 A continuous, at supply voltage OUTPUT B (START) 10 A short term, 5 A continuous, at supply voltage AUXILIARY OUTPUTS C, D, E & F 2 A DC at supply voltage